2711P-T12W21D8S

 

2711P-T12W21D8S Allen Bradley PanelView Plus 7 Standard Color Terminal, TFT 12.1-inch Touch Screen, Widescreen 1280 x 800 WXGA, Single Ethernet Port, 24V DC Power, Windows CE OS License, Standard Mode.

 

Attribute Value 2711P-T12W21D8S


Temperature, operating


6.5-in., 9-in., 10.4-in., 12.1-in., and 15-in. terminals
0…55 °C (32…131 °F)
19-in. terminals
0…50 °C (32…122 °F)(1)
ArmorView Plus 7 terminal
0…50 °C (32…122 °F) ambient(2)
(1) For Series B terminals, all terminal sizes, including the 19-in. terminal, having a temperature rating of 0…55 °C (32…131 °F).
(2) The optional I/O plate (included in the VESA Mounting Kit—2711P-RVESA01) is rated to 0…45 °C (32…113 °F).
Temperature, nonoperating -25…+70 °C (-13…+158 °F) (3)
(3) These values are the same for the ArmorView Plus 7 terminal.

Heat dissipation 2711P-T12W21D8S


Typical BTU measurements were taken at 25 °C (77 °F):
• 6.5-in. DC (touch, and touch with keypad), 51 BTU (typical) (Series B, 38 BTU)
• 6.5-in. AC (touch, and touch with keypad), 53 BTU (typical)
• 9-in. DC, 55 BTU (typical) (Series B, 41 BTU)
• 9-in. AC, 58 BTU (typical)
• 10.4-in. DC (touch, and touch with keypad), 51 BTU (typical) (Series B, 48 BTU)
• 10.4-in. AC (touch, and touch with keypad), 56 BTU (typical)
• 12.1-in. DC, 60 BTU (typical) (Series B, 49 BTU)
• 12.1-in. AC, 67 BTU (typical)
• 15-in. DC (touch, and touch with keypad), 61 BTU (typical) (Series B, 71 BTU)
• 15-in. AC (touch, and touch with keypad), 68 BTU (typical)
• 19-in. DC, 114 BTU (typical) (Series B, 92 BTU)
• 19-in. AC, 119 BTU (typical)
Altitude, operating 2000 m (6562 ft)(3)
Relative humidity 5…95% without condensation(3)

Vibration 2711P-T12W21D8S


6.5-in., 9-in., 10.4-in., 12.1-in. terminals, and 12.1-in. terminals in the ArmorView Plus 7 enclosure
0.012 pk-pk, 10…57 Hz
2 g peak at 57…500 Hz
15-in. and 19-in. terminals
0.006 pk-pk, 10…57 Hz
1 g peak at 57…640 Hz
Shock, operating 15 g at 11 ms(4)
(4) These values are the same for the ArmorView Plus 7 terminal when the VESA mount is used. When the arm mount coupling is used, the values are 5 g at 11 ms.
Shock, nonoperating 30 g at 11 ms(4)
Enclosure ratings NEMA and UL Type 12, 13, 4X, also rated IP66 as Classified by UL (5) (6)
(5) For the ArmorView Plus 7 terminal, the enclosure ratings are 12, 13, 4, or 4X (see the ArmorView Plus 7 Installation Instructions, publication 2711P-IN013 for more
detail) and IP66 as classified by UL.
(6) The PanelView Plus 7 Performance Stainless Steel Series B and Series C terminals are also rated IP69 as Classified by UL and tested for IP69K according to ISO
20653.


Corrosive Atmosphere


ASTM B845-97 Method K Accelerated Test
(30 Day Exposure)
Severity Level GX*,** per ANSI/ISA 71.04-2013, Airborne Contaminants – Gases
**up to 2100 angstroms of film growth per 30 days of copper and silver reactivity
Severity Level CX* per IEC 60721-3-3-2019, Chemically Active Substances
*Port plugs need to remain installed in unused ports at all times during storage and operation, for the
product to meet its corrosive atmosphere rating.