Selected:

6ES7332-5HF00-0AB0

6ES7332-5HF00-0AB0

Siemens 6ES7332-5HF00-0AB0 SIMATIC S7-300 SM332 Analog Cur/Volt Output, 8-Point

Description

6ES7332-5HF00-0AB0

 

Siemens 6ES7332-5HF00-0AB0  Simatic S7-300, Analog Output Sm 332. Optically Isolated, 8 Ao, U/I; Diagnostics; Resolution 11/12 Bits, 40 Pin, Remove/Insert W. Active, Backplane Bus / 6ES7332-5HF00-0AB0 New, Used and Refurbished.


LOAD VOLTAGE L+
  •     Rated value (DC)    24 V

INPUT CURRENT
  •   From load voltage L+ (without load), max.      340 mA
  •   From backplane bus 5 V DC, max.                    100 mA

POWER LOSSES
  •     Power loss, typ.  6W

ANALOG OUTPUTS
  •   Number of analog outputs   8
  •   Voltage output, short-circuit protection   Yes
  •   Voltage output, short-circuit current, max.   25 mA
  •   Current output, no-load voltage, max.   18 V

OUTPUT RANGES, VOLTAGE
  •   0 to 10 V    Yes
  •   1 to 5 V      Yes
  •   -10 to +10 V  Yes

OUTPUT RANGES, CURRENT
  •   0 to 20 mA  Yes
  •  -20 to +20 mA  Yes
  •  4 to 20 mA  Yes

LOAD IMPEDANCE (IN RATED RANGE OF OUTPUT)
  • With voltage outputs, min.  1 k?
  • With voltage outputs, capacitive load, max.  1 ?F
  • With current outputs, max.  500 ?
  • With current outputs, inductive load, max. 10 mH

CABLE LENGTH 
  •   Cable length, shielded, max.  200 m

ANALOG VALUE CREATION

Integrations and conversion time/ resolution per channel

  • Resolution with overrange (bit including sign), max. 12 bit ; +/-10 V, +/-20 mA, 4 to 20 mA, 1 to 5 V: 11 bits + sign; 0 to 10 V, 0 to 20 mA: 12 bits
  • Conversion time (per channel)  8 ms

SETTLING TIME
  • For resistive load  0.2 ms / For capacitive load  3.3 ms / For inductive load  0.5 ms ; 0.5 ms (1 mH); 3.3 ms (10 mH)

ERRORS / ACCURACIES

Operational limit in overall temperature range

  •  Voltage, relative to output área  +/- 0,5 %
  •  Current, relative to output área   +/- 0,6 %

BASIC ERROR LIMIT (OPERATIONAL LIMIT AT 25 °C)
  •  Voltage, relative to output área  +/- 0,4 %
  •  Current, relative to output área   +/- 0,5 %

INTERRUPTS/DIAGNOSTICS/STATUS INFORMATION
  • Substitute values connectable   Yes ; Parameterizable

ALARMS
  • Diagnostic alarm  Yes ; Parameterizable

DIAGNOSTIC MESSAGES
  • Diagnostic information readable  Yes
  • Diagnostics  Yes

DIAGNOSTICS INDICATION LED
  • Group error SF (red)  Yes

GALVANIC ISOLATION

Galvanic isolation analog outputs

  •   Between the channels and the backplane bus   Yes

ISOLATION
  • Isolation checked with  500 V DC

CONNECTION METHOD
  • Required front connector   40-pin

DIMENSIONS
  •  Width  40 mm
  •  Height  125 mm
  •  Depth  120 mm

WEIGHTS
  •   Weight, approx.  272 g

 